Cooling Tower Inspection & Clean

During a recent cooling tower inspection, we found a large build up of scale throughout the tower. We submitted a detailed report to the client complete with comprehensive photographic support.

wp741edd26_0f.jpg
wpe7070af0_0f.jpg

Scale in pack

wpd29f5723_0f.jpg

Scale in pack

wp0c7dcabc_0f.jpg

Air inlet panel

wp8bea81ab_0f.jpg

Air inlet panel

wp4cae3f38_0f.jpg

Scale out of bottom layer of pack

Scale out of one air inlet panel

wpf820fb24_0f.jpg
wpe18389cd_0f.jpg

Floor before clean

Floor before clean

wpaf1cb703_0f.jpg
wp93acebf3_0f.jpg

Scale from pack

Floor before clean

wp3e1e6e44_0f.jpg
wpb3e24623_0f.jpg

Floor after bagging scale

Floor after bagging scale

wp6a085bb2_0f.jpg
wp36c77014_0f.jpg

Splash guard before clean

Splash guard before clean

wp90762736_0f.jpg
wp51b6167f_0f.jpg
wp5ee7ab6a_0f.jpg

Splash guard after clean

Splash guard after clean

wpb3bb49f1_0f.jpg

Roof after clean

Roof before clean

wpb1bbb248_0f.jpg
wp5072d1af_0f.jpg

One old grommet, one new grommet

wp041cb1b3_0f.jpg

Spray nozzles - one new, one old

wpcad3ec73_0f.jpg

Blocked nozzle

Blocked nozzle

Cooling Tower Surveys

During a recent cooling tower survey, we found a huge build up of slime in the cooling towers which can harbour and provide nutrients for Legionella bacteria.

wpabcfc4ca_0f.jpg
wpf39d857f_0f.jpg

Above: Green slime and sediment in the cooling towers

Below: Sediment and slime in the pack

 

 

 

wp3a49ddfb_0f.jpg
wpe02db8c0_0f.jpg
wpcbbcb50f_0f.jpg

We recommended that the Legionella risk assessment and the water treatment programme be reviewed as a matter of urgency as we feel that the towers present a considerable risk at the moment. This was further compounded by the fact that the towers were observed to have large amounts of drift coming from the fan area whilst in operation.  As a precaution we recommended that the towers be cleaned every 3 months until the conditions are improved and the source of the slime has been identified.

 

 

Cooling Tower Deep Clean

This cooling tower was generally in a satisfactory condition.  Scale was removed with the aid of pressurised water and a scouring pad, and the fill pack was removed and cleaned with a mild acid solution to remove the scale.  The pond was cleaned using a submersible pump and vacuum to remove sediment and scale.  

 

Click on pictures for a full size view

wp1c71168f_0f.jpg
wp58aaddd2_0f.jpg

Tower wall before clean

Tower wall after clean

wp373a28a5_0f.jpg
wpd1a68c36_0f.jpg

Pond before clean

Pond after clean

wp13b10ae5_0f.jpg
wp3aa02787_0f.jpg

Fill pack and spray bars before clean

Fill pack and spray bars after clean

wp6bc005b0_0f.jpg
wpb9c8883e_0f.jpg

Scaled fill pack before clean

Fill pack after clean

wpe5832ce3_0f.jpg
wpc4ffa12f_0f.jpg

Tower internal before clean

Tower internal after clean

Cooling Tower Deep Clean

This cooling tower was extremely fouled with gelatinous deposits. The pack, air inlet panels and drift eliminators were removed and pressure washed to remove all of the deposits.  The tower sumps were vacuumed out and all internal surfaces were washed. We then replaced the clean tower pack infill, the drift eliminators and the air inlet panels for each cell.

 

Click on pictures for a full size view

wpb64d247d_0f.jpg

Slime in the pack prior to clean

wp85946ea9_0f.jpg

Foam and slime in the sump prior to clean

wp45236d75_0f.jpg

Fouled sump prior to clean

wp3e3d1e83_0f.jpg

Slime on the basin prior to clean

wp0da85630_0f.jpg

Foam and slime in the sump prior to clean

wp54aa2257_0f.jpg

Sump following clean

wpc35d3bca_0f.jpg

Pack following clean

Cooling Tower Inspections & Cleans

During cooling tower inspections, we found a large build up of scale throughout towers, dirty and collapsing air inlets, corrosion in drift eliminator frames, brittle drift eliminators and collapsing supports.

wp386af16e_0f.jpg
wp892d3804_0f.jpg
wp0bead0e7_0f.jpg

Air inlets

Air inlets

Cleaning air inlets

wp3739f58d_0f.jpg

Damaged air inlets

wp0dc3977e_0f.jpg

Repaired air inlets

wp7c4793d4_0f.jpg

Damaged drift eliminators

wp97f55a78_0f.jpg
wp6e2d890d_0f.jpg

Damaged pack

Collapse

wpab19f8f0_0f.jpg
wpcb800a83_0f.jpg

Brittle drift eliminators

Collapsing tower

wp33a53cca_0f.jpg
wp3616b8db_0f.jpg
wpeb4928bc_0f.jpg

Dirty trough

Dirty trough

Dirty trough

wp2786c7cf_0f.jpg

Drift eliminators with rusted frames

wpdeb19c40_0f.jpg

Timber pack repairs

wpffe4d640_0f.jpg

Dirty trough, almost completely full with debris